This outage hit FogBugz and Kiln On Demand customers and lasted from about 4:05PM GMT to 4:40PM GMT. If this outage affected you, please contact us so we can make it right.
This was a step-by-step repeat of Saturday's outage on a different rack. One PDU inexplicably failed and the second tripped a circuit breaker as it took over the load.
In light of this common component failure, additional steps are necessary to prevent a repeat of this event.
Short term, we are stripping our cabinets down to the bare minimum of redundancy. Should another PDU fail, the secondary will be able to handle the entire cabinet's load without exceeding the circuit's capacity. Certain components (like switches) that have only a single power input will need to be manually swapped over, but such an event would incur a much briefer outage. This will be completed by this evening.
Longer term, we are replacing half of our PDUs with APC models. Each rack will have one Tripplite and one APC PDU to eliminate the possibility of a single bad batch of components wiping out a cabinet. This timeframe is dependent upon our vendors, but it will be completed as soon as possible.
Thank you again for your patience.